How to Repressurise a Boiler
If your boiler has stopped working and the pressure gauge reads below 1 bar, you may simply need to repressurise it. This is one of the few boiler-related tasks that is safe for homeowners to carry out themselves — and most modern boilers use the same basic process.
This guide walks you through repressurising your boiler step by step, explains what equipment you'll need, and covers what to do if the pressure won't hold.
What is boiler pressure and what should it be?
Boiler pressure refers to the water pressure in your central heating system. Unlike mains water pressure (which comes from the supply), central heating is a sealed system — meaning the pressure needs to be maintained correctly to allow the pump to circulate water effectively.
For most combi and system boilers, the correct operating pressure when the system is cold is between 1 and 1.5 bar. When the heating is running and the system is warm, pressure will typically rise slightly to around 1.5–2 bar — this is normal and nothing to worry about.
If your pressure gauge reads below 1 bar when the boiler is cold, the system needs repressurising before the boiler will fire correctly.
What you'll need
On most modern boilers, repressurising is done via a filling loop — a short braided hose with a valve (or two valves) that connects the heating system to the cold mains water supply.
- Your boiler's instruction manual (to confirm the location of the filling loop)
- A flat-head screwdriver (some valves require one to open)
- A cloth or towel (to catch any small drips)
Step-by-step: how to repressurise your boiler
Step 1 — Turn the boiler off
Switch the boiler off completely and allow it to cool for at least 30 minutes before repressurising. Working on a hot system can cause scalding.
Step 2 — Locate the filling loop
The filling loop is usually located underneath the boiler or on the pipework nearby. It looks like a short, silver braided hose connecting two pipes, with one or two taps or valves. If you're unsure, check your boiler's manual or the label on the boiler casing.
Step 3 — Open the filling loop valve(s)
Turn the valve(s) slowly to the open position — usually a quarter turn so the slot in the valve aligns with the pipe. You should hear water entering the system. Watch the pressure gauge on the boiler (it may be on the front display or a separate dial).
Step 4 — Watch the pressure gauge
Allow the pressure to rise to 1.5 bar, then close the valve(s) firmly. Do not overfill — pressure above 2.5 bar when cold can trigger the pressure relief valve and cause water to discharge outside.
Step 5 — Switch the boiler back on
Restart the boiler and check the pressure is stable. On some boilers you may need to press the reset button after repressurising. Check for any drips from the filling loop once you're done — close the valves fully if you see any.
What if the pressure keeps dropping?
If you repressurise the boiler and find yourself doing it again within a few days or weeks, there is a leak somewhere in the system. This could be at a radiator valve, a pipework joint, the pressure relief valve, or inside the boiler itself.
A slow leak can be difficult to spot — the water may evaporate before it pools. A Gas Safe engineer can pressure test the system and identify the source. Do not ignore recurring pressure loss — it will get worse and can cause the boiler to lock out repeatedly.
Repressurising is a short-term fix if there is an underlying leak. Call WarmaHome on 01582 932324 if pressure keeps dropping after repressurising.
Need expert advice from a local engineer?
WarmaHome are Gas Safe registered boiler engineers covering Luton, Dunstable, Leighton Buzzard and Milton Keynes. We'll give you a straight answer and a fair price.
Frequently Asked Questions
Get expert help today
Gas Safe engineers in Luton, Dunstable, Leighton Buzzard & Milton Keynes.
Boiler Pressure Guide
Everything you need to know about boiler pressure — from low pressure and how to repressurise, to high pressure and what to check.
Boiler Pressure HubWhy WarmaHome?
- Gas Safe registered engineers
- Worcester Bosch Accredited Installer
- 4.9/5 from 1,250+ reviews
- Family-run since 2008
- Same or next-day available